Electro-magnetic interference (EMI) and leakage currents
3.1.3

Converter unit (FR-CC2) built-in EMC filter

The converter unit (FR-CC2) is equipped with a built-in EMC filter (capacitive filter).
These filters are effective in reducing air-propagated noise on the input side of the converter unit.
To enable the EMC filter, fit the EMC filter ON/OFF connector to the ON position.
Both of two EMC filter ON/OFF connectors are initially set to the OFF position (disabled).
To enable the EMC filter, fit the both EMC filter ON/OFF connectors to the ON position.
<How to enable or disable the filter>
• Before removing a front cover, check to make sure that the indication of the inverter operation panel is OFF, wait for at least
10 minutes after the power supply has been switched OFF, and check that there is no residual voltage using a tester or the
like.
• When disconnecting the connector, push the fixing tab and pull the connector straight without pulling the cable or forcibly
pulling the connector with the tab fixed.
When installing the connector, also engage the fixing tab securely.
(If it is difficult to disconnect the connector, use a pair of needle-nose pliers, etc.)
EMC filter
ON/OFF connector
(Side view)
NOTE
• Fit the connector to either ON or OFF position.
• Enabling (turning ON) the EMC filter increases leakage current. (Refer to
WARNING
 While the inverter power is ON, do not open the front cover. Otherwise you may get an electric shock.
78
PRECAUTIONS FOR USE OF THE INVERTER
EMC filter ON/OFF connector
EMC filter OFF
EMC filter ON
EMC filter ON/OFF connector
OFF ON
OFF ON
EMC filter OFF
EMC filter ON
Disengage connector fixing tab
With tab disengaged,
pull up the connector straight.
page
73.)