Introduction; Scope Of Manual; Technical Assistance - GE Becker 3.5M Series Instruction Manual

Digital natural gas positioner with modbus protocol
Table of Contents

Advertisement

Introduction

The DNGP is designed specifically for the needs of the
Natural Gas industry. By using solenoids to control the
actuator pressures, the DNGP eliminates the continuous
bleed gas produced by I/P transducers and bleeds no
gas until the valve is called upon to move. The DNGP
can even do this while maintaining a pressure difference
across the actuator. Additionally, the discharge can
be directed downstream, and the positioner is capable
of failing in last position on a loss of signal, DC power
or power gas. Reliability and simplicity have been
engineered into the DNGP, while features that make the
positioner versatile, easy to use, and fail safe, have been
retained.

Scope of Manual

This manual provides information on the installation,
adjustment, and maintenance of the DNGP-Digital
Natural Gas Positioner. For information concerning
actuators, valves, and accessories, refer to the
instruction manuals provided with the specific product.
Table 1 - DNGP Technical Specifi cations
Electrical Power Requirements
Over Current Protection
Position Input Signal (Selectable) Standard
Transmitter Feedback Signal
Remote Indicator Dual Function Output
Valve Position Feedback Module
Display
Input Mode Selection
Electrical Manual Override
Communications
Solenoid Bypass
Loss of Signal Options (Selectable)
Position Input Signal Impedance
Transmitter Feedback Input Signal Impedance transmitter)
2

Technical Assistance

Only those qualifi ed through training or experience
should install, operate, or maintain Becker position-
ers. Should you have any questions concerning these
instructions, you may contact your local GE sales
representative, sales offi ce, or manufacturer before
proceeding.
GE Energy
Becker Control Valves
Attn: Technical Assistance
1550 Greenleaf Avenue
Elk Grove Village, IL 60007
Toll Free:
+1-800-323-8844
Telephone:
+1-847-437-5940
Fax:
+1-847-437-2549
web: ge.com/energy
VIN = 12 to 24 VDC nominal (11-30 VDC) 21 VDC min. for 24 VDC Sole-
noid, 11 VDC min. for 12 VDC Solenoid 1 to 2 A including DNGP heater
and transmitter heater (3 A fuse line recommended)
20 Joule, 2000 A surge and lightning transient protection 3 A fuse for
Logic module 24 VDC power 50/150 mA PTC resettable fuses for posi-
tion input signal and transmitter feedback signal
4-20 mA (Split Range: 4 mA min. up to 16 mA max. in 1 mA increments),
minimum 4 mA band
Analog Rotary: External or Internal Digital Linear: Internal only; RTU
Feedback must be dry
Outputs VIN-1.5V @ 20 mA max. (for example if VIN = 24 VDC, this
supplies 22.5 ± 0.5 V)
The remote Indicator function can be selected to function as "Solenoid
Counter" or "In Standby/Manual". In Counter mode it pulses whenever
either solenoid activates. In Standby/Manual mode, it is active
whenever the DNGP is in Standby or Manual modes.
Primary: Linear Digital Transmitter Analog Rotary Types Also Available:
80 (4 x 20) character Vacuum Fluorescent Display for: Command
Signal, Valve Position Feedback, Solenoid Cycle Count (stored in 10 year
non volatile memory), Dead Band value. Incorporates a user
navigational menu system.
Manual/Auto/Standby
Manual pushbutton positioning (must engage Manual Mode with Auto/
Manual/Standby Switch)
DNGP Dashboard PC Interface, Modbus
Can be ON or OFF within 1.5% of the end stroke (in full closed and
open position).
Drive to 4 mA position (open or closed valve position) Drive to 20 mA
position (open or closed valve position) Lock in last controlled position
120 to 220 Ω
120 to 220 Ω (additional operating voltage required for
communication protocol