Installation and operating instructions
QX³ series
DANGER from fire
Fire resulting from insufficient fuse protection of the PV inputs or the PV strings
NOTE
The relevant DC string configuration must be configured in the display
(Installation Assistant) (see Chapter 5.17) or via the web server (see Chapter 7
Operation and monitoring via the web interface).
CAUTION
If the DC string configuration is not configured correctly, the MPP cannot be
optimised. There is risk of loss of yield.
The plus and minus connections of different MPP trackers must not be
connected to each other.
The following threshold values for the DC input of the inverter must not be
exceeded:
Threshold values at the DC
Device
QX³4000
QX³5000
QX³6000
QX³7000
QX³8000
QX³10000
QX³13000
QX³15000
QX³18000
3
Pay attention to short-circuit currents in the modules (parallel circuit of several strings)
4
Minimum operating Temperaturee
_____________________________________________________________________________________________
Q3 ENERGIE Installation and operating instructions QX³ series
Version 1.0, Stand 27.04.2015
Max. MPP current
Max. short circuit current
10A
10A
10A
18A/10A
18A/10A
18A
18A
18A
18A
3
Maximum voltage with T
12A
12A
12A
20A/12A
20A/12A
20A
20A
20A
20A
4
min
1000V
1000V
1000V
1000V
1000V
1000V
1000V
1000V
1000V