Installation and operating instructions
QX³ series
Dimensioning of the grid supply cable
Select the cross-section of the AC grid supply cable in such a way that the cable
losses are kept as low as possible (max. possible cross-section, with min. cable
length).
The following table shows the maximum cable lengths in dependence on the
cable cross section. The maximum cable length should not be exceeded in order
to limit the ohmic voltage drop in the cable to < 1%.
Cable length
Device
QX³4000
QX³5000
QX³6000
QX³7000
QX³8000
QX³10000
QX³13000
QX³15000
QX³18000
_____________________________________________________________________________________________
Q3 ENERGIE Installation and operating instructions QX³ series
Version 1.0, Stand 27.04.2015
Max. Current
Minimum cable cross-section
8A
10A
12A
20A
22A
25A
Max. Cable length
5x 1, 5mm²
5x 2,5 mm²
5x 4 mm²
5x 1,5 mm²
5x 2,5 mm²
5x 4 mm²
5x 1,5 mm²
5x 2,5 mm²
5x 4 mm²
5x 4 mm²
5x 6 mm²
5x 10 mm²
5x 4 mm²
5x 6 mm²
5x 10 mm²
5x 4 mm²
5x 6 mm²
5x 10 mm²
24 m
40 m
64 m
19 m
32 m
51 m
16 m
26 m
43 m
25 m
38 m
64 m
23 m
35 m
58 m
20 m
31 m
51 m