No.
Failure Status
9.
Power trouble
10.
Line card trouble
11.
Field device trouble
12.
Automatic interlocking
failure
13.
Manual control failure
14.
Disable/enable failure
15.
Test/restore failure
16.
Display failure of fire
alarm, activation, trouble
17.
Query history event
failure
18.
Site programming
(modifying) failure
19.
Printer open/close failure
20.
Other operations failure
Operating Manual of FC18 Controller
Cause Analysis
Configuration file does not consist with actual
equipment;
External voltage exceed power requirement;
Battery is damaged;
Power is damaged;
Configuration file does not consist with actual
equipment;
Address is not set by dip-switch on line card
or dose not consist with configuration file;
Line card is damaged;
Trouble of FD18-US signal line, power line
Severe damage of field device;
Wiring trouble;
Configuration file does not consist with actual
equipment;
Address is not set by dip-switch on field
device or does not consist with configuration
file;
Field device is damaged;
Controller and interlocking panel are not in
automatic status;
Logic expression is not set, or wrong;
Interlocking equipment is damaged;
Power, interlocking lines is damaged;
User level is wrong;
Controller and interlocking panel are not in
manual status;
Interlocking equipment is damaged;
Power, interlocking lines is damaged;
User level is wrong;
Operation method is wrong;
Main board is damaged;
User level is wrong;
Operation method is wrong;
CPU is damaged;
Software trouble;
CPU is damaged;
Operation method is wrong;
Part of main board is damaged;
User level is wrong;
Operation method is wrong;
CPU is damaged;
User level is wrong;
Operation method is wrong;
Power, signal lines connection;
Software configuration trouble;
Printer is damaged;
User level is wrong;
Operation method is wrong;
Software lost or error;
Some hardware is damaged;
Recommend Solving Method
Change configuration file;
Adjust external voltage range;
Change battery;
Change power supply;
Change.configuration file;
Set address by sip-switch or Change
configuration file;
Change line card;
Check communication line, power line
Change the damaged. field device;
Examine wire connections;
Change configuration file;
Change configuration file;
Change damaged field device;
Change configuration;
Set/change logic expression;
Change damaged interlocking
equipment;
Examine wire connections;
Login higher user level;
Change configuration;
Change damaged interlocking
equipment;
Examine wire connections;
Login higher user level;
Operate correctly;
Change main board;
Login higher user level;
Operate correctly;
Change CPU;
Update software;
Change CPU;
Operate correctly;
Change main board;
Login higher user level;
Operate correctly;
Change CPU;
Login higher user level;
Operate correctly;
Connect wires correctly;
Update software;
Change printer;
Login higher user level;
Operate correctly;
Update software;
Change corresponding hardware;