Appendix 6: Additional features for customization

Required setting for proper functionality
Parameters
ZXDE
ZXDI
A19
P7C
C05
LS
Compressor regulation probe selection
G01
EcS
G02
SEt
G03
Hy
Positive differential defines upper cut-in temperature
Parameters
ZXDE
ZXDI
R07
i3F
R08
i3P
Parameters
ZXDE
ZXDI
G42
FnC
S05
oA2
G45
Fon
G46
FoF
G55
Fnd
C6.1.10/0118-0318/E
Temperature sensor in case temperature – System restart is required!
Parameter description
Probe 7 configuration
Case temperature probe selection
Cut-out temperature
Unit On/Off – System restart is required!
Parameter description
Digital input 3 configuration
Digital input 3 polarity
Evaporator fan – System restart is required!
Parameter description
Fans operating mode
Relay output 2
Fan on time
Fan off time
Fan delay after defrost
Setting needs to be adjusted according to application
Factory setting
nu = Not used
SuP = Suction pressure
probe
nu = Not used
+2°C
1K
Factory setting
nu = Not used
CL = Closed
Factory setting
cn = Switch on and off with the compressor, stop
cn
cy = Switch on and off with the compressor, run
nu = Not used
1 min
1 min
1 min
Required setting
tnt = Thermostat temperature
CSt = Case temperature
tnt = Thermostat temperature
Adjust to application requirements
Adjust to application requirements
Required setting
OnF = On/Off
Adjust to application requirements
Required setting
during defrost
On = Always on, stop during defrost
during defrost
Oy = Always on, run during defrost
EPF = Evaporator fan
Adjust to application requirements
Adjust to application requirements
Adjust to application requirements
60