Emerson Copeland EazyCool ZXDI Series Application Manuallines page 55

Indoor condensing units
Table of Contents

Advertisement

Parameters
ZXDE
ZXDI
H03
tLS
Voltage sensing 1
H04
CS1
Voltage sensing 2
H05
CS2
Voltage sensing 3
H06
US1
Voltage and current protection enabled
H07
US2
Maximum continuous current limit
H08
US3
Voltage/current sensing trip minimum off time
H09
CSE
Adjustable current limit before trip
H10
MCC
Ignore current sensing duration at start-up duration
H11
dMC
Number of over current trips before lock
H12
MC2
Number of loss of phase trips before lock
H13
diC
Minimum voltage to trip compressor
H14
oCn
Maximum voltage to trip compressor
H15
PEn
Over or under voltage minimum time
Compressor minimum off time because of voltage
H16
LUo
error
Number of compressor trips before lockout because
H17
HUo
of voltage
H18
dUA
Adjustable under average voltage percentage
Generate warning or shut down compressor when
H19
Uot
phase imbalance
H20
Utn
Missing current duration before warning
H21
PiP
Minimum high side superheat
Amount of time allowed in an interval to check for
H22
PiC
floodback
H23
CMd
Interval to check for floodback
Duration of checking anti-floodback alarm reset
H24
LHS
condition
H25
tFb
Three-phase enable
Ambient temperature threshold to off crankcase
I01
iFb
heater
C6.1.10/0118-0318/E
Description
no; yes
no; yes
no; yes
no; yes
3PE = 0: 0.0 to 70.0 A
3PE = 1: 0.0 to 35.0 A
0 to 255 min
0.0 to MCC Ampere
0 to 255 sec
0 to 15
0 to 15
0 to 400V
0 to 800V
0 to 255 sec
0 to 255 min
0 to 15
0 to 100%
0: Generate warning (0-ARN)
1: Unit off(1-Off)
0 to 255 sec
-40 to 110°C
0 to H23 min
H22 to 120 min
1 to 255 min
no; yes
-40°C to 180°C
Range
Factory setting
NO
NO
NO
YES
Unit dependent
5
9.5
3
5
5
360
480
60
3
5
90
Unit off
10
10
30
45
20
YES
10
ZXDI
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
N.V.
N.V.
L2
L2
L2
L2
L2
L2
L2
L2
N.V.
N.V.
L2
L2
50