Emerson Copeland EazyCool ZXDI Series Application Manuallines page 45

Indoor condensing units
Table of Contents

Advertisement

Parameters
ZXDE
ZXDI
C16
LMO
Digital compressor setpoint
C17
LAP
Proportional band for compressor regulation
C18
StC
Band offset for compressor regulation
C19
Pbd
Integral time
Start-up time: interval time with digital valve
C20
rS
energized before regulation starts
C21
inC
Cycle time for digital compressor
C22
SUt
Safety value for PI regulator (in case of probe error)
C23
tdG
Number of active compressor when probe error
C24
SPi
Minimum capacity for digital compressor
C25
SPr
Maximum capacity for digital compressor
C26
PMi
Time with DGS at PMA before starting another load
Time with DGS at PMi before switching off another
C27
PMA
load
C28
ton
R404A Enable function
C29
toF
R507 Enable function
C30
Er0
R134a Enable function
C31
Er1
R22 Enable function
C32
Er2
R407C Enable function
C33
Er3
R407A Enable function
C34
Er4
R407F Enable function
C35
Er5
R448A Enable function
C36
Er6
R449A Enable function
C37
Er7
R410A Enable function
C38
Er8
Compressor regulation control signal
D01
Er9
Output delay at start-up
D02
dEU
Compressor On time with faulty probe
D03
odS
Compressor Off time with faulty probe
D04
Con
Minimum time between two starts (same compressor) 0 to 15 min
C6.1.10/0118-0318/E
Description
LS to US
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to
25.5°C
0 to 9.9 bar; 0 to 99.9 PSI; 0.0°C to 25.5°C
0 to 999 sec
0.0 to 10.0 sec
10 to 40 sec
0 to 100%
0 (0) – 1 (1) – 2 (2)
0 to PMA
PMi to 100
0 to 255 sec
0 to 255 sec
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Disable (0-NO) - Enable (1-YES)
Pressure (0-PRS) - temperature (1-TMP)
0 to 255 sec
0 to 255 min
0 to 255 min
Range
Factory setting
3.3
2
0
250
10
20
50
0
20
100
0
0
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Pressure
5
0
0
4
ZXDI
L1
L1
L2
L2
L2
L1
L2
L2
L1
L1
L2
L2
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
N.V.
L2
L2
L2
L2
L2
40