The unit will be turned on for the minimum run time when the low-pressure input is closed.
If the pressure drops below the cut-out value or the low-pressure input opens, the unit should
continue to run for the remaining minimum on time (C14/LAS) or until a satisfactory condenser
pressure is reached (C13/LAd).
If a suction pressure transducer is present and the suction pressure falls below a given value
(C15/LAT) during the minimum on time (C14/LAS), then disregard the timer and shut the
compressor off to protect against vacuum operation.
NOTE: For additional features please contact your local Application Engineering
representative.
2.11 XCM25D Electronic controller – Programming
CAUTION
Low refrigerant charge! Compressor damage! Never energize the
unit/controller without minimum refrigerant system charge. There is a risk of
malfunction of the controller in deep vacuum operation which can cause
compressor damage.

2.11.1 Programming the local display

Figure 9: Local display

LED
Mode
On
Flashing
On
On
Flashing
On
Flashing
On
Flashing
On
Flashing
On
On
On
Table 10: LED functions description
NOTE: By default, the local display will show the value of the suction pressure during
operation. This can be changed by choosing another value for parameter B03/Lod (Remote
Display visualization).
12
Function
Compressor 1 enabled
Anti-short cycle delay enabled
Condensing fans enabled
Bar display
Programming mode
PSI display
Programming mode
When browsing the service menu
In fast access menu
When browsing the alarm menu
A new alarm occurred
An alarm is occurring
Digital unloader solenoid On
In defrost