Parameters
ZXDE
ZXDI
R07
i3F
Digital input 3 function
R08
i3P
Digital input 3 polarity
R09
d3d
Activation delay for digital input 3
S01
ALC
Alarm contact activation in a warning, alarm, lockout
S02
tbA
Alarm relay deactivation
S03
bEn
Buzzer enabled
S04
oA1
Relay output 1 configuration
S05
oA2
Relay output 2 configuration
S06
oA3
Relay output 3 configuration
S07
oA4
Relay output 4 configuration
S08
oA5
Relay output 5 configuration
S09
oA6
Triac output 1 configuration
S10
oA7
Triac output 2 configuration
S11
oA8
EXV configuration
C6.1.10/0118-0318/E
Description
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
oP (0) - CL (1)
0 to 255 min
Warning (0-ARN) - Alarm (1-ALM) -
Lockout (2-LOC)
No (0-NO) - Yes (1-YES)
No (0-NO) - Yes (1-YES)
Not used (0-NU)
DGS compressor (1-DGS)
On-Off compressor (2-CPR)
Condenser fan 1 (3-CF1)
Condenser fan 2 (4-CF2)
Evaporator fan (5-EPF)
Defrost (6-DEF)
Crankcase heater (8-HTR)
Alarm (9-ALM)
Light (10-LIG)
Not used (0-NU)
Digital solenoid (1-DGT)
Wave-form chopper for fan speed (2-PCF)
PWM fan speed (3-PEF)
0-10V (4-UEF)
Not used (0-NU)
Digital solenoid (1-DGT)
Wave-form chopper for fan speed (2-PCF)
Not used (0-NU)
Liquid injection EXV (1-LIN)
EVI EXV (2-UIN)
System EXV (3-SHT)
Range
Factory setting
Not used
CL
0
Alarm
YES
NO
Crankcase heater
Not used
Digital Scroll
compressor
Not used
Alarm
Digital solenoid
Wave-form chopper for
fan speed
Not used
ZXDI
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2