Emerson Copeland EazyCool ZXDI Series Application Manuallines page 57

Indoor condensing units
Table of Contents

Advertisement

Parameters
ZXDE
ZXDI
M15
dbd
Interval of updating valve
M16
LPr
Filter on the temperature [1-100] sec
M17
HPr
Activation delay probe error
M18
FiP
% Valve in case of probe error
M19
iEU
Time at initial steps at the start time
N01
Fit
Current minute
N02
tPE
Current hour
N03
PEP
Day of month
N04
tSS
Month
N05
Min
Year
Compressor setpoint hysteresis in energy saving
P01
Hr
mode
Condenser setpoint hysteresis in energy saving
P02
MdY
mode
R01
Mon
Digital input 1 function
R02
YEr
Digital input 1 polarity
R03
ESC
Activation delay for digital input 1
R04
i2F
Digital input 2 function
R05
i2P
Digital input 2 polarity
R06
d2d
Activation delay for digital input 2
C6.1.10/0118-0318/E
Description
1 to 255 sec
1 to 255 sec
0 to 255 sec
0 to 100%
0 to 255 sec
0 to 59
0 to 23
1 to 31
1 to 12
0 to 99
0.0 to 9.9 bar; 0. to 99.9 PSI;
0.0°C to 25.5°C
0.0°C to 25.5°C
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
oP (0) - CL (1)
0 to 255 min
Not used (0-NU)
Suction pressure switch (1-SUS)
Thermostat input (2-DEF)
High pressure input (3-HP)
Low pressure input (4-LP)
Door switch (5-DOR)
Energy saving enable (6-ES)
On/Off (7-ONF)
oP (0) - CL (1)
0 to 255 min
Range
Factory setting
20
1
1
50
30
0
0
Not used
CL
0
High pressure input
oP
0
ZXDI
L2
L2
L2
L2
L2
L1
L1
L1
L1
L1
L2
L2
L2
L2
L2
N.V.
N.V.
N.V.
52