System Evacuation And Charging - Carrier 38MPRA Series Service Manual

Outdoor unit single zone ductless system. sizes 09 to 24
Hide thumbs Also See for 38MPRA Series:
Table of Contents

Advertisement

SYSTEM EVACUATION AND
CHARGING
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. Always break a
vacuum with dry nitrogen.
System Vacuum and Charge
NOTE: DO NOT open the service valves until unit
evacuation procedure is complete.
Using Vacuum Pump
1. Completely tighten all the flare nuts and connect the manifold gage
charge hose to a charge port of the low side service valve (see Fig.
9).
2. Connect the charge hose to the vacuum pump.
3. Fully open the low side of the manifold gage (see Fig. 10).
4. Start the vacuum pump.
5. Evacuate using the triple evacuation method.
6. After the evacuation is complete, fully close the low side of
manifold gage and stop the vacuum pump operation.
7. The factory charge contained in the outdoor unit is good for up to
25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft. (8
m), add refrigerant as specified in the "Additional Charge Table" on
page 13.
8. Disconnect the charge hose from the charge connection of the low
side service valve.
9. Fully open the service valves; B and A.
10. Securely tighten the service valve caps.
Refrigerant
Outdoor Unit
A
B
Service Valve
Fig. 9 — Service Valve
Manifold Gage
500 microns
Low side valve
Low Side Hose
Unit service valve
(requires 5/16" to 1/4"
Schrader adapter for
evacuation/charging)
Fig. 10 — Manifold
14
Indoor Unit
Gas Side
C
D
Liquid Side
High side valve (remains closed)
Charge hose
Vacuum pump
Specifications subject to change without notice.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling
a vacuum of 500 microns and a vacuum gage capable of accurately
measuring the vacuum depth. The deep vacuum method is the most
positive way of assuring a system is free of air and liquid water (see
Fig. 11).
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
1
2
Fig. 11 — Deep Vacuum Graph
Triple Vacuum Method
The triple evacuation method should be used. Refer to Fig. 12 and
proceed as follows:
1. Pump the system down to 1500 microns and allow the pump to
continue operating for an additional 15 minutes.
2. Close the service valves and shut off the vacuum pump.
3. Connect a dry nitrogen cylinder and regulator to the system and
break the vacuum until the system reaches 2 psig.
4. Close the service valve and allow the system to stand for 1hr.
During this time, the dry nitrogen can diffuse throughout the system
absorbing moisture.
5. Pump the system down to 1000 microns.
6. Break the vacuum with dry nitrogen (2 psig).
7. Pump the system down to 500 microns.
8. Perform the hold test for 30 minutes.
EVACUATE TO 1500 MICRONS
BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS
BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY
Fig. 12 —Triple Evacuation Method
Final Tubing Check
IMPORTANT: Ensure that the factory tubing, on both the
indoor and outdoor units, has not shifted during shipment.
Ensure tubes are not rubbing against each other or any
sheet metal. Pay close attention to feeder tubes to ensure
the wire ties on the feeder tubes are secure and tight.
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
3
4
5
6
7
SG-38MPRA-02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38mpraq09aa338mpraq12aa338mpraq24aa338mpraq18aa3

Table of Contents