Terminal assignments of AS-i safety monitors ASM1/2 and ASM1E/2
Terminal
Signal / description
AS-i+
Connection to the AS-interface
bus
AS-i–
L+
+24V DC / supply voltage
M
GND / reference ground
FE
Functional earth
1.Y1
EDM 1 / input of external de-
vice monitoring circuit, output
circuit 1
1.Y2
Start 1 / start input, output
circuit 1
Output switching element 1,
1)
1.13
output circuit 1
1.14
1)
Output switching element 2,
1.23
output circuit 1
1.24
1.32
Message output 1 "Safety on",
output circuit 1
2.Y1
EDM 2 / input of external de-
vice monitoring circuit, output
circuit 2
2.Y2
Start 2 / start input, output
circuit 2
1)
Output switching element 1,
2.13
output circuit 2
2.14
Output switching element 2, output circuit 2
1)
2.23
2.24
2.32
Message output 2 "Safety on", output circuit 2
1) Safeguard according to technical data