Example of how to calculate the maximum detection distance
Calculate the maximum detection distance for a heptane fire, 0.1 m
flame detector has a 'Normal' detector sensitivity and a vision angle of 0°.
Known:
S
Correction coefficient for detector sensitivity
Gg Fire size wanted
Gb Basic fire size
K
Correction coefficient for directional sensitivity
F
Correction coefficient for fuel
Gg
´
´
d =
S
K
Gb
The maximum detection distance is 21 m.
In order to calculate the maximum mounting height h, you need to know detection
distance d.
Formula for calculating maximum mounting height h
d
h =
3
h Mounting height
Example of how to calculate the maximum mounting height
Calculate the maximum mounting height given a detection distance of 21 m.
Known:
Detection distance d = 21 m
The maximum mounting height is 12 m.
2
0.1 m
´
´
F
= 23 m
2
0.25 m
d Detection distance
in size. The
2
23
0.1 m
0.25 m
1
1.5
´ 1 ´ 1.5 = 21.82 m