Specifications
8
Technical data
Ambient conditions
Mechanical data
Standards
60 | 66
Building Technologies
Fire Safety
Operating temperature:
Storage temperature
Air humidity
Protection category (IEC 60529):
Electromagnetic compatibility:
1 MHz...1 GHz
1 GHz...2 GHz
Dimensions (L x W x H)
Weight:
Base for flame detector
Flame detector
Material:
Base for flame detector
Flame detector
Color
European standards
-35...+70 °C
-40...+75 °C
95 % rel.
IP67
50 V/m
30 V/m
135 x 135 x 77 mm
0.25 kg
0.5 kg
ABS/PC-Blend
Aluminum casting
RAL 9010 pure white
EN 54-10
EN 54-17
007011_m_en_--
2018-06-28