7.3 Repair

Building Technologies
Fire Safety
Problem
The flame detector does not activate an alarm during the performance check.
Remedy
Ensure that the flame detector is registered on the control panel.
l
If the problem persists:
Ensure that the protective glass on the flame detector is clean and the sensors
l
are clearly visible. Clean the protective glass if this is not the case.
If the problem persists:
Replace the flame detector.
l