3 Viewing and Changing MJ-5 Data Items
Changing Alpha or Numeric Settings
The process of changing alpha or numeric settings is
similar to that of changing configuration parameters, except
that there are more choices because there may be multiple
characters to change, and each character may range in value
from 0 to 9, and/or A-Z.
Example
Suppose you want to change the regulator Forward Volts
set point from 123.0 volts to 122.5 volts. Set points are
contained in the <REGULATOR> menu, so you need to
view that menu.
1.
Press the Menu key twice to return the display to the
<METER> menu.
Press the ► key until <REGULATOR> is viewed.
2.
Press the ▼ key until FwdVolts: 123.0 appears with
3.
the indicator arrow => to the left of it.
4.
Press the Change/Save key to activate Change mode.
(The flashing digit indicates the digit to be changed.)
FwdVolts: appears with 123.0 beneath it. Note: the
underscore in this section of the manual (in this case
under the 0) denotes flashing.
Press the ▲ key five times to increment the digit from
5.
0 to 5.
Press the ◄ key to step left one digit. 123.5 now
6.
appears. The digit 3 is flashing to indicate that it can
be changed.
Press the ▼ key to decrement the digit from 3 to 2.
7.
8.
Press the Change/Save key to make the change take
effect. The data item list appears and FwdVolts: 122.5
is present.
9.
Alternative to step 8. If you do not want to save the
changes made, press the Cancel/Reset key to exit
change mode without changing any values.
Siemens Industry, Inc.
3.5 Using the Fast-Path Keys to View/
Change Data Items
Fast-path keys are the labeled keys on the middle portion of
the MJ-5 Control Panel, such as the Voltage Level key.
Use the Fast-path keys as a shortcut to certain frequently
used data items. Simply press the fast-path key and the
desired data item appears immediately.
After viewing an item with a fast-path key, the change
procedure is the same as the one just described. In the
previous example, the Voltage Level fast-path key would
replace steps 1-3 and save a number of key strokes.