Appendix K
2.
Read Total Ops count on display
3.
Press Op Count key repeatedly to step through
remaining counter values
View Messages
1.
Press Alert Fast-Path key
2.
Read and note active alerts on display
3.
Press Alert key repeatedly to step through remaining
active alerts
4.
While viewing alerts, press Cancel Reset key to
acknowledge an alert
5.
Note: Acknowledging alert does not clear the fault that
caused the alert
Configure the Control Panel
1.
Press Menu key twice
2.
Press Right Arrow key five times to view the
<CONFIGURE> menu
3.
Press Up/Down Arrow key to display the desired item.
4.
Press Change/Save key
5.
Press Left Arrow or Right Arrow to step through digits
in numeric values
6.
Press Up/Down Arrow to toggle through text choices
or to increase or decrease numeric values
7.
Press Change/Save key to save the new value
8.
Repeat steps 3 through 7 for all desired configuration
items
View/Set the Clock (Time and Date)
1.
Press Menu key twice
2.
Press Right Arrow key six times to view the <ADV
CONFIGURE> menu
3.
Press Down Arrow until the TIME item is displayed.
It will be in Military time.
4.
Press Change/Save key - the left hand digit will flash
5.
Press Up/Down Arrow key to increase or decrease the
value
6.
Press Left Arrow to step to next digit.
7.
Press Change/Save key to save the new time
8.
Press Down Arrow key to display the DATE item
Siemens Industry, Inc.
:
MJ-5 Operating Procedures
9.
10. Press Up/Down Arrow key to increase or decrease the
11. Press Right Arrow to step to the next digit to be
12. Press Change/Save key to save the new date
Using a Voltmeter to Calibrate U2 or P2
Note: Do not use voltage readings at the Voltage
Calibration (Test) terminals as an indication of the
regulated load voltage
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. See Manual Chapter 6 for additional calibration
Set Tap Position
1.
2.
3.
4.
Press Change/Save key - the left hand digit will flash
value
changed
NOTE: The date format (MM/DD or DD/MM) may
be changed using the DtFormat menu item in Adv
Configure menu.
Connect true-RMS-reading voltmeter to Voltage
Calibration (Test) terminals
Press U2 P2 key to display U2 (or P2) Cal item on the
display.
If voltmeter reading is not the same as U2 (or P2) Cal
item, press Change
At password prompt, press Up/Down Arrow key to
enter first digit of password (See Manual Chapter 4)
Press Right Arrow key to step through remaining
digits and enter values
Press Change/Save key to submit password
If password is correct, press Change/Save key – right
hand digit will flash
Press Up/Down Arrow key to increase or decrease
value until U2 (or P2) Cal value is equal to the
voltmeter value
Press Change/Save key to save the new calibration
value
procedures
Display Tap= in <COUNTERS> menu
Press Change/Save key
Press Up/Down Arrow key until reading matches
regulator Position Indicator value
Press Change/Save key to save new value.
77