Siemens MJ-5 Installation And Operation Manual page 103

Voltage regulator control panel
Hide thumbs Also See for MJ-5:
Table of Contents

Advertisement

CustomTap
100% configurable, all <Diagnostic > menu configurations unlocked
Default Values
Due to storage limitations, once a tap changer is selected, the default values are set. The MJ-XL has no
method of recalling the previous value(s) for another changer type. In short, once the changer type is
changed the modified Configuration will be wiped from memory and replaced with the default values. The
default values are as follows:
Parameter
Siemens
R/L On Time:
8.0
R/L Off Time:
0.0
Tap Change T/O:
0.0
TapIn Signal:
U10
TapInType:
TOGGLE
TapInPulse:
0.00
PreTapTime:
0.2
PostTapTime:
1.2
Neutral In:
U12
NeutralCount:
1
Siemens Industry, Inc.
GE
COOP SD
8.0
8.0
3.0
3.0
3.0
3.0
U10
HS
PULSE
PULSE
0.02
0.02
0.5
0.5
0.5
0.5
U12
U112
1
1
COOP DD
LTC (D-Star)
0.5
5.0
3.0
2.0
3.0
3.0
HS
U10
PULSE
PULSE
0.60
1.00
0.5
0.2
0.5
1.2
U112
NONE
1
1
LTC .5
0.5
3.0
3.0
U10
PULSE
0.6
0.5
0.5
NONE
1
98