Chapter 2 Specifications; Performance Specifications - Mitsubishi Electric RJ51AW12AL User Manual

Melsec iq-r anywireaslink master module
Hide thumbs Also See for RJ51AW12AL:
Table of Contents

Advertisement

2
SPECIFICATIONS
2.1

Performance Specifications

The following table lists the performance specifications of the RJ51AW12AL.
Item
Transmission clock
Maximum total wiring length
Transmission system
Connection type
Transmission protocol
Error control
Number of bit data points/number of word data points
Number of connected slave modules
External interface (power supply part/communication
part)
*3
Transmission cable (DP, DN)
*3
Power supply cable (24V, 0V)
Applicable solderless terminal
*2
Transmission cable supply current
Maximum number of writes to EEPROM
Internal current consumption (5VDC)
External power supply
Number of occupied I/O points
External dimensions
Height
Width
Depth
Weight
*1 For slave modules with transmission cables (DP, DN), the length of the transmission cables (DP, DN) is included in the total wiring
length.
For wiring of 50m or more with 4 wires (DP, DN, 24V, 0V), insert the noise filter for power supply cables between the power supply and
cables. For details, refer to the manual for the AnyWireFILTER (ANF-01) manufactured by Anywire Corporation.
*2 For the relation of the total wiring length, wire diameter of transmission cables (DP, DN), and transmission cable supply current, refer to
the following.
On some slave modules with cables, the wire diameter of module-integrated transmission cables (DP, DN) may be smaller than
0.75. However, they can be used without any problem, provided that the wire diameter of transmission cables (DP, DN) meets the
following requirements.
Wire diameter of transmission
cables (DP, DN)
1.25
0.75
*3 When the operating ambient temperature is 50 or higher, use cables with a temperature rating 75 or higher.
*4 The performance specification differs depending on the production information of the RJ51AW12AL. ( MELSEC iQ-R
AnyWireASLINK Master Module User's Manual (Application))
Description
27.0kHz
*1
200m
DC transmission line total frame cyclic transmission cyclic system
Bus topology (multidrop system, T-branch system, tree branch system)
Dedicated protocol (AnyWireASLINK)
Checksum, double-verification system
• Number of bit data points: 512 bits maximum (input 256 bits/output 256 bits)
• Number of word data points: 1024 words maximum (input 512 words/output 512 words)
128 maximum (varies depending on the current consumption of each slave module)
Push-in type 7-piece spring clamp terminal block ( Page 28 Terminal Block)
• UL-listed general-purpose 2-wire cable (VCTF, VCT 1.25, 0.75, temperature rating 70 or
higher)
• UL-listed general-purpose wire (1.25, 0.75, temperature rating 70 or higher)
• Dedicated flat cable (1.25, 0.75, temperature rating 90)
• UL-listed general-purpose 2-wire cable (VCTF, VCT 0.75 to 2.0, temperature rating 70 or
higher)
• UL-listed general-purpose wire (0.75 to 2.0, temperature rating 70 or higher)
• Dedicated flat cable (1.25, 0.75, temperature rating 90)
• Processing of a 1.25 wire: AI 1,5-8 BK
• Processing of a 0.75 wire: AI 0,75-8 GY
• When using a 1.25 cable: 2A maximum
• When using a 0.75 cable: 1.2A maximum
100000 times maximum
0.2A
Voltage: 21.6 to 27.6VDC (24VDC -10 to +15%), ripple voltage 0.5Vp-p or lower
Recommended voltage: 26.4VDC (24VDC +10%)
Transmission cable supply current: 2A maximum
32 points (I/O assignment: intelligent 32 points)
106mm (base unit mounting part: 98mm)
27.8mm
124mm
0.13kg
Transmission cable supply current
Total wiring length of 50m or
less
2A maximum
1.2A maximum
*2
Total wiring length of 50 to
100m
1A maximum
0.6A maximum
2.1 Performance Specifications
*4
Total wiring length of 100 to
200m
0.5A maximum
0.3A maximum
2 SPECIFICATIONS
2
17