BM-2 programming unit
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set DHW temperature is reached.
If the maximum cylinder heating time is exceeded, DHW mode is interrupted for the duration of the set maximum
cylinder heating time (WP022).
ECO setting:
In the ECO setting, the heat pump tries to reach the selected set DHW temperature or set minimum DHW temperature.
After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated.
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set minimum DHW temperature is achieved.
If the maximum cylinder heating time is exceeded, DHW mode is terminated, provided the set minimum DHW
temperature has already been achieved.
Otherwise DHW mode is interrupted for the duration of the set maximum cylinder heating time (WP022).
25.5.4 Day temperature
Day temperature is only enabled if the room influence is enabled for this heating/mixer circuit and the BM-2 is
installed in the wall mounting base.
Use the day temperature to set the required room temperature in heating mode, party function mode and the heating
phases during automatic mode.
In setback mode, economy mode and during the setback phase in automatic mode, the room temperature is only
regulated to the day temperature less the economy factor.
25.5.5 Room influence
Room influence is only active if the BM-2 programming unit is installed as a remote control.
Room influence can be used to compensate for fluctuations in room temperature due to external sources of heat and
cold (e.g. insolation, woodburning stoves or open windows).
ON = room influence enabled
OFF = room influence disabled
When room influence is on, the standard setting "Day temperature" (for heating mode) is available and, for systems
with active cooling, the standard setting "Day temperature, cooling" (for cooling mode).
25.5.6 Day temperature, cooling
"Day temperature, cooling" is only enabled if the room influence is enabled for this heating/mixer circuit and the BM-2
is installed in the wall mounting base.
"Day temperature, cooling" allows you to set the required room temperature in active cooling operating mode during
automatic operation.