22.6 Electrical connection (low voltages)
Connecting input E1
Push connecting cable through cable entry.
Connect the connection cable for input E1 to terminals E1.
No external voltage may be connected to input
Please
E1, as this could destroy the component.
note
Connecting input E2/SAF
Push connecting cable through cable entry.
Connect the connection cable for input E2/SAF to terminals
E2/SAF.
Only one external voltage of max. 10 V may
Please
be connected to input E2/SAF, otherwise the
note
PCB will be destroyed.
1(a) = 10 V, 2(b) = GND
5 k NTC header sensor SAF; alternatively 0-10 V or floating
contact
Connecting the outside sensor
The outside sensor can be connected to the terminal strip
of the heat pump at connection AF, or to the terminal strip
of the control accessories.
No external voltage may be connected to input
Please
AF, as this will destroy the component.
note
Connecting the cylinder sensor
Push connecting cable through cable entry.
Connect the lead for the SF cylinder sensor to the
SF terminals.
No external voltage may be connected to input
Please
SF, as this will destroy the component.
note
Connecting digital WOLF control accessories
(e.g. BM-2, MM, KM, SM1, SM2)
Only controllers from the WOLF range of accessories may
be connected. Each accessory is supplied with its own
connection diagram.
Use a two-core cable (cross-section > 0.5 mm²) as the
connecting cable between the control accessory and the
BWL-1S (1 is + and 2 is -).
When installing the appliance in places where
Please
there is a risk of increased electromagnetic
note
interference, it is advisable to fit screened
sensor leads and eBUS cables. The cable
shield should be connected at one end to the
PE potential in the control unit.
3064298_201805
Indoor module electrical connection
2
Figure: Input E1 connection
2
Figure: Input E2/SAF connection
Figure: Outside sensor AF connection
Figure: Cylinder sensor SF connection
Figure: Connecting digital WOLF control accessories (eBUS interface)
230 V~
230 V~
230 V~
2
230 V~
2
230 V~
2
47