AM display module

24.5 Description

(Selection and more details in the AM display module instructions.)
24.5.1 DHW operating mode
Comfort setting:
In the Comfort setting, the heat pump tries to reach the set DHW temperature.
After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated.
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set DHW temperature is reached.
If the maximum cylinder heating time is exceeded, DHW mode is interrupted for the duration of the set maximum
cylinder heating time (WP022).
ECO setting:
In the ECO setting, the heat pump tries to reach the selected set DHW temperature or set minimum DHW temperature.
After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated.
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set minimum DHW temperature is achieved.
If the maximum cylinder heating time is exceeded, DHW mode is terminated, provided the set minimum DHW
temperature has already been achieved.
Otherwise DHW mode is interrupted for the duration of the set maximum cylinder heating time (WP022).
24.5.2 DHW quick heat-up
If the DHW quick heat-up standard setting is on, the DHW temperature is regulated once to the set DHW temperature
configured on the AM/BM-2, using all available heat generators. The standard setting is then automatically reset.
24.6 Energy saving mode
No function.
24.6.1 Active cooling
Enables the user to activate/deactivate active cooling.
This requires, amongst other things, that the system is configured with active cooling and that active cooling is
enabled via contractor parameter WP058 (factory setting: OFF).
(See chapter "Additional functions".)