Electrical Connection (230 V) - Wolf BWL-1S-05 Installation And Operating Instructions Manual

Split air/water heat pump
Hide thumbs Also See for BWL-1S-05:
Table of Contents

Advertisement

22.5 Electrical connection (230 V)
230 V mains connection
The control and safety devices are fully wired and tested.
You only need to connect the power supply and the external
accessories.
Create a permanent connection for the power supply.
Provide the power supply via a mains isolator (e.g. heating
system emergency stop switch) that ensures at least 3 mm
contact separation for all poles.
No other consumers may be connected to the cable. In
rooms with a bathtub or shower, the appliance may only be
connected via an RCD.
The indoor module power supply must not have
power-OFF or a shutdown tariff.
Installation information – electrical connection
- Isolate the system from the power supply before opening.
- Remove the front casing.
- Open the integral casing cover.
- Check that the appliance is isolated from the power supply.
- Push the cable through the cable entry.
- Pull out the Rast5 plug.
- Terminate the appropriate cores at the Rast5 plug.
Connecting output Z1 (230 V AC; max. 1.5 A) *
Push connecting cable through cable entry.
Connect the cable to terminals L1, N and
* Max. 1.5 A / 345 VA per output; sum of all outputs
no more than 600 VA
3064298_201805
Indoor module electrical connection
.
Netz
Z1
L1
L1
L1
3
Figure: Mains connection
Netz
Z1
L1
L1
L1
3
Figure: Output Z1 connection
HKP
A1
3WV
N
L1
N
L1
HKP
A1
3WV
N
L1
N
L1
45