The password can be reset to the default password 1111 by resetting the password in the Modbus register.
Menu navigation is not allowed after 10 wrong attempts. After 10 wrong attempts, reset the password to the
default value. The password cannot be reset through the HMI.
After entering the correct password, you can access the parameters menu. If no key has been pressed during
30 minutes, the parameter menu is closed and the home screen is displayed.
In the battery mode, changing the password is not allowed.
NOTE
i
i
The password has 4 digits. Each digit ranges from 0 to 9. The password 0000 is invalid.
NOTE
i
i
By default, the password protection is disabled.

Device Alerts

4.1.37
The device can detect and indicate overvoltage alarms and warnings, undervoltage alarms and warnings, and
overcurrent alarms and warnings when it is in service. The device alerts are communicated via Modbus and
displayed on the user interface. The alerts reset automatically when the current/voltage falls below the
threshold levels again or exceeds them again in case of an undervoltage.
Undervoltage Alarm and Undervoltage Warning
The undervoltage alerts are enabled when the system voltage falls below the user-defined setting (V
Alarm/V
Warning). The threshold is defined in percentage of rated primary voltage. For more information
min
about the undervoltage alarm and undervoltage warning, see
Undervoltage Warning and Undervoltage Alarm menu.
Overvoltage Alarm and Overvoltage Warning
The overvoltage alerts are enabled when the system voltage exceeds the user-defined settings (V
V
Warning). The threshold is defined in percentage of rated primary voltage. For more information about
max
the overvoltage alarm and overvoltage warning, see
voltage Warning and Overvoltage Alarm menu.
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Password Menu Access
Table A-4
and refer to the Fault Parameters >
Table A-4
and refer to the Fault Parameters > Over-
Device Functions
4.1 Description
min
Alarm/
max
57