Determination Of Fault Direction - Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

If the phase sequence is clockwise, then it is denoted as ABC. Similarly if the phase sequence is counter-clock-
wise, then it is denoted as ACB. The monitored phase sequence is also displayed as 2 discrete inputs in the
Modbus register.
The following phasor diagram shows the clockwise and counter-clockwise phase sequences:
[dw_sfcm-phasesequence, 1, en_US]
Figure 4-9
In the HMI, the status of the phase sequence is shown as PH SEQ: ABC or PH SEQ: ACB or ---, if the phase
sequence cannot be determined.
If the phase sequence is ABC, then the discrete input (33) of the Modbus register is set to 1.
If the phase sequence is ACB, then the discrete input (34) of the Modbus register is set to 1.
If the phase sequence is not detected, then the discrete inputs (33, 34) of the Modbus registers are set to 0.
If the phase-to-ground voltage is below the threshold voltage, then the phase sequence is displayed as --- on
the HMI and the Modbus register is set to 0.
If there are any device alerts and a fault is detected in the system, then the phase sequence is displayed as ---
on the HMI and the Modbus register is set to 0.
NOTE
i
i
Protection functions implemented in SICAM FCM are designed for clockwise phase sequence only.

Determination of Fault Direction

4.1.15
The fault direction for the phase faults is determined by calculating the phase angles between the fault
current and the corresponding phase-to-phase voltages.
Pickup
Measuring Element
1
1
I
1
2
3
N
1, N
I
1
2, N
3, N
6
V
= V
+ V
+ V
(derived value)
NG
1
2
3
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Clockwise and Counter-Clockwise Phase Sequences
2
V
- V
2
3
I
2
V
- V
2
3
I
2
3
V
- V
3
1
I
V
3
1
V
- V
3
1
I
V
3
1
Device Functions
4.1 Description
N
- V
2
6
V
NG
I
V
6
N
NG
I
V
6
N
NG
- V
I
V
6
2
N
NG
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents