Device Technical Data - Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Technical Data

5.1 Device Technical Data

5.1
Device Technical Data
Technical Data
Medium-voltage and low-voltage application range
Frequency range
Auxiliary power-supply voltage range
Integrated back-up battery
Measuring Inputs for Voltage (MLFB 6MD2321-1AA00-1AA0)
Rated voltage ph-n
Measuring range
Internal impedance
Measuring Inputs for Voltage (MLFB 6MD2322-1AA00-1AA0)
Measuring range
Internal impedance
Measuring Inputs for Current (according to IEC 60044-8, IEC 61869-10)
Rated voltage
Internal impedance
Measuring range phase current (225 mV@300 A
sensor)
Measuring range ground current (225 mV@60 A
sensor)
Thermal load capacity (current inputs)
Measured-Value Accuracy
Measured Variable
8
Voltage V
Phase current I
Frequency f (47 Hz to 53 Hz/57 Hz to 63 Hz)
Energy measurement accuracy
For optimum battery capacity, Siemens recommends storing the device below 30 °C; 30 % RH
7
The accuracy of voltage measurements is up to 0.5 % (±10 % of the rated voltage) for MLFB 6MD2321-1AA00-1AA0.
8
9
The accuracy of current measurements is up to 0.5 % (100 A to 600 A) for MLFB 6MD2321-1AA00-1AA0.
62
9
1 kV to 36 kV
45 Hz to 65 Hz
DC 24 V to 250 V (± 10 %)
AC 230 V (± 20 %)
Battery lifetime for 15 years
AC 3.25/√3 V, AC 100/√3 V, AC 230 V
0.075 V to 3 V for 3.25/√3 (according to
IEC 61869-11)
3 V to 250 V for 100/√3 V
15 V to 250 V for 230 V
200 kΩ
3 V to 50 V
20 MΩ
225 mV
> 20 kΩ
1 A to 6000 A
0.2 A to 1200 A
4.5 Vrms (continuous)
Accuracy Class Depending on IEC
61557-12:2007-08 (K55)
0.5 %
1 % for MLFB 6MD2322-1AA00-1AA0, for secondary
VDS voltage at 30 V
1 A or 0.5 % at rated frequency
1 %
1 % for a duration of 1 h
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
7