4.8.5.3

Transmission settings - ST7

Transmission settings
● Send conditional spontaneous frames as blocks
Indicates the form of transfer of data frames with the transmission mode "Conditional
spontaneous".
– Option enabled
– Option disabled
The transfer mode (Spontaneous / Conditional spontaneous) of a frame is set in the
"Trigger" tab of the data point.
● Max. allowed disruption time
Tolerance time (s) for a detected connection disruption.
If there is still a disruption on the connection when the set time has elapsed, the
disruption is signaled to all accessible connection partners of the disrupted station.
Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled.
4.8.5.4
Transmission settings – DNP3
Transmission settings – DNP3
● Disturbance bit
The disturbance bit can be used as bit 1.6 (IIN1.6) of the "Internal Indication Bytes" to
indicate to the master when the CPU is in STOP mode.
● Max. time between Select and Operate
Max. duration (seconds) between Select and Operate. For a Select command to be
transferred to the CPU and to take effect, no other frame may be sent to the station
between Select and Operate.
Permitted range: 1..65535
Default setting: 1
● Frame repetitions
Number of frame repetitions at the Data Link Layer if no acknowledgement is received
from the master.
Permitted range: 0 ... 255
Default setting: 0
If you enter 0 (zero), the function is disabled.
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
Several items of data are collected and only sent when a frame has reached
maximum capacity.
The data is sent spontaneously as individual frames.
Configuration
4.8 Ethernet interface
75