MAW
Initial value of the measuring range
MEW
Final value of the measuring range
ASP
Analogue start point
AEP
Analogue end point
Table 1: Definitions
1
[mA]
FOU=On
22
21,5
20
4
FOU=OFF
3,5
cr.UL UL
Q
-130
T
-50
-58
Figure 1: Characteristics of the analogue output according to the standard IEC 60947-5-7�
Q:
Flow (a negative flow value means flow against the marked flow direction)
T:
Temperature
UL:
Below the display range
OL:
Above the display range
cr�UL:
Below the detection zone (error)
cr�OL:
Above the detection zone (error)
FOU=On:
Default setting at which the analogue signal goes to the upper final value in
case of an error�*
FOU=OFF: Default setting at which the analogue signal goes to the lower final value in
case of an error�*
* The type of error is displayed: cr�UL, cr�OL, Err (→ 12)�
8
5*
6*
MAW
ASP
-120
0
-40
-20
-40
-4
For non-scaled measuring range
(= factory setting)
For scaled measuring range
3
4
5
6
AEP
MEW
100
80
176
2
OL
cr.OL
120
130
[% MEW]
100
110
[°C]
212
230
[°F]