Advertisement

Section 7 • Alarms and Trips
Oil Pressure Safety Bypass timer times out.
Low Oil Injection Temp Trip
• This message will appear when the Oil Injection tem-
perature falls below the Low Oil Injection Temperature
trip setpoint. This message will also appear when the
Oil Injection temperature fails to rise above the Low
Oil Injection Temperature reset setpoint after the
Low Oil Injection Temp Bypass timer times out.
High Oil Injection Temp Trip
• This message will appear when the Oil Injection
temperature rises above the High Oil Injection
Temperature trip setpoint.
High Filter Differential Trip
• This message will appear if the Filter Differential
Pressure rises above the High Fltr Diff Press – Start
setpoint before the Filter Differential Pressure Safety
Changeover timer times out.
High Filter Differential Trip
• This message will appear if the Filter Differential
pressure rises above the High Fltr Diff Press Run
setpoint after the Filter Differential Pressure Safety
Changeover timer times out.
High Motor Current Trip
• This message will appear if the motor amperage rises
above the Hi Motor Amps trip setpoint.
Compressor Interlock Trip
• This message will appear if the Motor Auxiliary con-
tact fails to close before the Compressor Starter
Auxiliary Contact Bypass timer times out. Refer to
wiring diagram.
High Level Shutdown Trip
• This message will appear when power is removed
from the input module that is designated as "Auxiliary
#1 Safety" Refer to wiring diagram.
False Start
• This message appears when the compressor stops
and the motor auxiliary contact fails to open. The
message will also appear if the compressor shuts
down and the amperage is 20% of the maximum amp
setting, indicating that the starter is still energized.
Low Oil Level Trip
• This message appears when power is removed from
the designated input module, refer to wiring dia-
gram. This safety will activate only after the oil level
has been low for the time period defi ned by the "Low
Oil Separator Safety Trip Delay" timer.
7 – 6

Compressor Warnings

High Level Shutdown Warning
• This message will appear when High Level Shutdown
switch is Active Low.
Low Process Temp Warning
• This message will appear when Process Control
Temperature
Low Process Temperature Alarm setpoint.
High Discharge Pressure Warning
• This message will appear when the Discharge
Pressure exceeds the safety setting of the High
Discharge Pressure Alarm setpoint.
High Discharge Temp Warning
• This message will appear when the Discharge
Temperature exceeds the safety setting of the High
Discharge Temperature Alarm setpoint.
Low Suction Pressure Warning
• This message will appear when Suction Pressure falls
below the safety setting of Low Suction Pressure
Alarm setpoint.
Low Suction Temp Warning
• This message will appear when Suction Temperature
falls below the safety setting of Low Suction
Temperature Alarm setpoint.
Low Oil Separator Start Temp Warning
• This message will appear when the Oil Separator
Temperature falls below the safety setting of the Low
Oil Separator Start Temp Alarm setpoint.
High Oil Injection Temp Warning
• This message will appear when the Oil Injection
Temperature exceeds the safety setting of the High
Oil Injection Temp Alarm setpoint.
High Filter Differential Warning
• This message will appear when the Filter Differential
Pressure exceeds the safety setting of the High Filter
Diff Start Pressure Alarm setpoint.
High Superheat Temp Warning
• This message will appear when the Discharge
Superheat Temperature exceeds the safety setting of
the High Superheat Start Temp Trip setpoint.
Analog Aux in 1-16 Warning
• This message will appear when the Analog Aux in
1-16 exceeds / falls below the safety setting of the
High / Low Alarm setpoint.
Digital Aux in 1-16 Warning
• This message will appear when the Digital Aux in 1-8
is Active High / Low.
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9
falls below the safety setting of the