Section 13 • Instruments Calibration
uncommon for there to be a small error. By entering
the value of the error from the calibrated value and
the actual value into the adjustment entry box, that
error will be added/subtracted from the total offset.
The offset is applied to the calibrated value which
should correct the error.
Range:
• Here the operator defi nes the signal type and range
transmitted by the instrument. The operator can
choose from several predefi ned ranges in the drop-
down box or enter a value.

Figure 13-5. Instruments Calibration Screen - Analog Inputs (Page 5)

Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9