3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.10 Configuring Mode CAE4/CAE5 -- Setting UNI Module(s)
The corresponding settings of the CAE4(5) menus for the different signal transmitters are de-
scribed below.
The range and thus the current measured value can be corrected with the parameters CA/CE to
compensate tolerances of the transmitters or adjustments with other display instruments.

3.3.10.1 Measuring Range for mV (SEnS=Mv.)

D MA/ME measuring range
Call parameters MA, ME, set range start and end:
--175 mV ≤ MA ≤ ME +175 _C
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.

3.3.10.2 Measuring Range for U, I (SEnS=Mv.)

D MA/ME range
The setting is made in mV (--175 mV to +175 mV);
The input signal types U and I are set to range 0/20 to 100 mV in the measuring range plug
(6DR2805--8J);
Example:
0 to 10 V or 0 to 20 mA:
2 to 10 V or 4 to 20 mA:
Call parameters MA, ME, set range start and end:
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
164
MA = 0,
ME = 100;
MA = 20,
ME = 100
Manual
SIPART DR24 6DR2410
C79000-G7476-C153-03