3.3.10 Configuring Mode CAE4/CAE5 -- Setting UNI Module(s)

The measuring ranges for the various selectable signal transmitters for slot 2 (AE4) or slot 3
(AE5) can be defined in these menus and fine adjustment performed if necessary.
The CAE4 menu is only offered in the selection level if AEF is set at uni._ or uni. in the config-
uring mode hdEF.
The CAE5 module is only offered in the selection level if AE5 is set to uni._ or uni. in the con-
figuring mode hdEF.
In the uni._ selection the corresponding measuring signal is set to 0 in the event of a sensor
failure, in uni. selection to 1.
An error message will appear if the UNI module is not available: OP.. / 2,3..
The following parameters are available in the CAE4/CAE5 menus for setting the measur-
ing range and adjustment:
Display
Parameter
dd2 para-
meaning
meter
SEnS
Sensor type
unit
Temperature unit
tc
Thermocouple
type
1)
tb
Temperature refe-
rence point
Mr
Line resistance
Cr
Calibration line re-
sistance
MP
Decimal point
measuring range
2)
MA
Range start
2)
ME
Range end
3)
CA
Calibration range
start
3)
CE
Calibration range
end
4)
PC
Preset calibration
1)
If no specified type of thermocouple is selected with tc=Lin, parameter tb is inactive.
2)
The set range normalizes the measured value to 0 to 1 for transfer to the switchable range. If the physical operating
display of the measuring value is to be made, the assigned display dd, dA, dE must be set accordingly.
3)
For SEnS=r._/r.
the unit of the CA/CE display is in %.
4)
Effect PC for SEnS = Mv., tc.in, tc.EH, Pt.2L, Pt.3L, Pt.4L.
PC=no C is displayed with A=E=0. It is not possible to switch to "YES" with tA2.
PC=no is displayed by adjusting CA/CE (fine calibration). It is possible to switch to "YES".
Fine calibration is reset by pressing the Enter key (3s). (ΔA=ΔE=0, PC=no C).
SIPART DR24 6DR2410
C79000-G7476-C153-03
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.10 Configuring Mode CAE4/CAE5 -- Setting UNI Module(s)
Display dd1
Meaning of parame-
Parameter
ter
range
Mv.
Mv signal
tc.in
Thermocouple internal
reference point
tc.EH
Thermocouple external
Reference point
Pt.4L
PT100 4--wire
Pt.3L
PT100 3--wire
Pt.2L
PT100 2--wire
r.--
Resistor < 600 Ω
r.
Resistor < 2.8 kΩ
Degrees Celsius
_C
Degrees Fahrenheit
_F
Degrees Kelvin
_AbS
L,J,H,S,b,r,E
Type L,J,K,S,B,R,E,N,T,U
n,t,U
Any type (without li-
Lin
nearization)
0.0...400.0
0.00...100.00
Difference to
Mr
_.------ to ____
--1999...19999
--1999...19999
curr. measured
value
+/-- ΔA
curr. measured
value
+/-- ΔE
no,YES,no C
Factory
Display unit
setting
Mv.
_C
L
50.0
_C, _F, _AbS
10.00
ohms
ohms
___.--
0.0
Mv, _C, _F, _AbS
100.0
depending on set-
ting SEnS
3 Operation
Display/func-
tion only at
:
SEnS=tc.in,
tc/EH
SEnS=tc.EH
SEnS=Pt.2L
SEnS=Pt.2L
SEnSE!=r._, r.
163