Power supply

Compact instrumentation with FEW 52
Transistor circuit for load
The load connected to terminal 3 is switched by a transistor, contactless and therefore without
bouncing. In normal switching status, terminal 3 has a positive signal.
The transistor is blocked in the event of a level alarm or a power failure.
Protection against voltage peaks
When connecting a device with high inductance, always connect a voltage limiter.
FEW 52
1
2
F
L+
L–
Mains
Connecting the FEW 52 electronic insert.
– F: Fine-wire fuse 500 mA, semi-time lag
– M: Ground connection to protective earth
Power supply (FEW 52)
Supply voltage: U= 10.8 V...45 V
Load connection: open collector; PNP
Switching voltage: max. 45 V
Connected load, continuous: max. 200 mA
Protected against reverse polarity
Power consumption
P < 1.1 W
Current consumption
I < 25 mA (without load)
M
3
(+)
R
L00-FTW3xxxx-04-05-xx-en-001
9