3. Configuration level

For access to this level press
To switch to the next/previous configuration point (depending on the scrolling direction mode) press
Inside the configuration level it is not possible to switch over to the manual mode.
3.1
Optimisation
Selection:
Optimisation is triggered by:
When tunE is shown cyclically in the setpoint display SP then the optimisation process is running.
optimisation from manual mode
Set target setpoint SP
Switch to manual mode
By opening/closing the actuator the actual value PV
is set on a higher/lower value than the
target setpoint (a)
Wait until PV is in a stable state (b)
Switch over to configuration level
Set "OPt = 1"
To optimise a PI-controller set derivation action time
"td = 0"; to optimise a PID-controller set "td ≠0"
If known, set process gain "P.G"
(usual setting: P.G = 100%)
Back to operating mode
Switch over to automatic mode. Thereby optimisation is
W. Bälz & Sohn GmbH & Co.
>2s (see 2.5).
for automatic determination of favourable control parameters.
0 No optimisation
1 optimisation activated
manual mode:
switch over to automatic mode by pressing
automatic mode: changing the setpoint SP (not for external setpoint)
Procedure of optimisation:
Koepffstraße 5
D-74076 Heilbronn
6490B / 6490B-y / 6590B
optimisation from automatic mode
Set initial setpoint SP
Wait until PV is in a stable state (b)
Switch over to configuration level
Set "OPt = 1"
To optimise a PI-controller set derivation action time
"td = 0"; to optimise a PID-controller set "td ≠0"
If known, set process gain "P.G"
(usual setting: P.G = 100%)
Back to operating mode
Set target setpoint SP. Thereby optimisation
is started, "tunE" and the manipulated variable appear
alternate, actuator changes
During the optimisation process no inputs or
switch over are tolerated