Alarm Type Selection For Alarm Relay; Scaling The Process Variable Display Pv; Second Setpoint Sp.2 At 6X90B(-Y) /1 /4 /4-I - Baelz Automatic 6490B Device Manual

Microprocessor-based controller mcelsitron, universal three-position step controller
Table of Contents

Advertisement

Device manual
3.8
Decimal point for LED displays
Selection:
After any change of the decimal point the process variable display PV has to be rescaled (see 3.9 dI.L, dI.H).
By changing the decimal point, several other inputs of the configuration level are concerned. Because of the
high degree of accuracy of some inputs approximation errors may be possible.
3.9

Scaling the process variable display PV

Display low: enter zero point of the measuring range.
Defines the starting point for the PV indication related to the measuring range whereat dI.L < dI.H.
Setting range (depending on dP): -999 ... 9999 [phys. units] at dP = 0
Standard value: 0°C and 32°F respectively
Display high: enter final point of the measuring range.
Defines the final point for the PV indication related to the measuring range whereat dI.H > dI.L
Setting range (depending on dP): -999 ... 9999 [phys. units] at dP = 0
Standard value: 300°C and 572°F respectively
- When changing dI.L or dI.H, all values entered as physical units are rescaled expressed as
percentage
- When a Pt100 sensor is used, dI.L and dI.H have to correspond to the Pt100 measuring range of the
device (see type plate)
baelz 6490B / 6490B-y / 6590B - 2.4 - ... : dI.L = 0, dI.H = 300
baelz 6490B / 6490B-y / 6590B - 2.2 - ... : dI.L = 0, dI.H = 400
3.10 Setpoint limiting
Setpoint low: lowest setpoint which can be set
Setting range: dI.L to SP.H [phys. units] (see also 3.9 dI.L)
Effective for the setpoint adjustable via front keyboard.
Setpoint high: highest setpoint which can be set
Setting range: SP.L to dI.H [phys. units] (see also 3.9 dI.H)
Effective for the setpoint adjustable via front keyboard.
- If the range of dI.L/dI.H is changed, SP.L/SP.H is automatically set according to it expressed as
percentage.
- When SP.L = SP.H, the setpoint is fixed to this value. Changing the setpoint is not possible.
- When SP.L > SP.H, only between these two values can be switched via front keyboard. After
setting SP.L > SP.H, the last entered setpoint is displayed in the operating level.
The two fixed setpoints can be selected by pressing
3.11 *Second setpoint SP.2
Setting range: dI.L to dI.H [phys. units] (see also 3.9 dI.L, dI.H)
When the digital input assigned to SP.2 is active, the corresponding value becomes the actual setpoint
(see also 3.21-3.25 Assigning the digital inputs).
W. Bälz & Sohn GmbH & Co.
0 Display without decimal point: ####
1 Display with decimal point (1 decimal): ###.#
-0.999 ... 9.999 [phys. units] at dP = 3. See also 3.8 dP.
-0.999 ... 9.999 [phys. units] at dP = 3. See also 3.8 dP.
SP.L, SP.H
at 6x90B(-y) /1 /4 /4-i
Koepffstraße 5
D-74076 Heilbronn
6490B / 6490B-y / 6590B
dP
2 Display with 2 decimals: ##.##
3 Display with 3 decimals: #.###
dI.L, dI.H
or
and adjusted by pressing
SP.2
Telefon (07131) 1500-0
Page 17
.
* option
Telefax (07131) 1500-21