Baelz Automatic 6490B Device Manual page 32

Microprocessor-based controller mcelsitron, universal three-position step controller
Table of Contents

Advertisement

Device manual
Configuration point
Delta setpoint
Process gain
Measured value filter
Sensor break PV
Manual/automatic switch over
Direction of effect of controller
Assign a function to the
digital input
Second setpoint
OPEN
CLOSE
STOP
Calibration correction
Y-synchronization
Baud rate *
Address *
Serial communication *
* option
W. Bälz & Sohn GmbH & Co.
Display
Setting
Remarks
0 to ± scope of measuring range [phys. unit]
dSP
P.G
1% to 255%
FIL
0 to 255, complies with 0ms to 10s
SE.b
0
Actuator closes
1
Actuator opens
2
Actuator persists in its current position
1
only in automatic mode
MAn
0
Switch over via front keyboard
1
Interlocking in the current status "automatic"
Interlocking in the current status "manual"
dIr
0
Heating controller
1
Cooling controller
0 to 5 *
Defining the number of the digital input. 0 = inactive
S2.d
OP.d
CL.d
St.d
0 to ± scope of measuring range [phys. unit]
C.CO
Y.SY
0
- Y-bargraph is displayed
- actuator closes for the time of the valve actuating time
- internal Y-position = 0%
- actual Y-position is not saved in case of a mains failure
1
- Y-bargraph is displayed
- actuator does not close for the time of the valve actuating time at mains recov.
- internal Y-position = 0%
- actual Y-position is not saved in case of a mains failure
2
- Y-bargraph is displayed
- actuator does not close for the time of the valve actuating time at mains recov.
- actual Y-position is saved in case of a mains failure
- lastest saved Y-position is displayed at mains recovery
3
- Y-bargraph is displayed
- actuator does not close for the time of the valve actuating time at mains recov.
- actual Y-position is not saved in case of a mains failure
- latest saved Y-position is displayed at mains recovery
4
- Y-bargraph is not displayed, synchronization like at Y.SY = 0
5
- Y-bargraph is not displayed, synchronization like at Y.SY = 1
6
- Y-bargraph is not displayed, synchronization like at Y.SY = 2
7
- Y-bargraph is not displayed, synchronization like at Y.SY = 3
bd
0
19200 baud
1
9600 baud
2
4800 baud
3
2400 baud
Adr
1 to 247
Slave address at bus mode
Address
S.C
0
Operation of the controller via front keyboard and modbus-master is possible
1
Operation of the controller is only possible via modbus-master except
configuration point S.C
Koepffstraße 5
D-74076 Heilbronn
6490B / 6490B-y / 6590B
1
1
1
Telefon (07131) 1500-0
Page 32