Device manual

9. Overview of configuration level, data list

Configuration point
Optimisation
Proportional band
Three-position controller
Integral action time
Two-position controller
Derivative action time
Dead band
Valve actuating time
Alarm 1
Alarm 1, type A (at AL.1=1)
Alarm 1, type B (at AL.1=2/4)
Hysteresis for A1.A/A1.b
Alarm 1, type C lower limit
(at AL.1=3)
Hysteresis, lower limit for A1.C HY.1
Alarm 1, type C upper limit
(at AL.1=3)
Hysteresis, upper limit for A1.C HY.1.
Decimal point
Scaling low
Scaling high
Setpoint limiting low
Setpoint limiting high
Second setpoint *
Setpoint ramp
Ramp direction, time unit
* option
W. Bälz & Sohn GmbH & Co.
Display
Setting
Remarks
OPt
0
No optimisation
1
Optimisation active
Pb
1.0% to 999.9%
Pb =
0
tn > 0; db = dead band
tn
1s to 2600s
tn =
0
db conforms to switching hysteresis
td
1s to 255s; PI-control at td = 0
db
0 to 10th part of the scope of the measuring range [phys. units]
0 to + scope of the measuring range [phys. units] at dP = 3
t.P
5s to 300s
AL.1
0
No alarm, also not in case of sensor failure
1
Alarm A, depending on the setpoint, also in case of sensor failure
2
Alarm B, fixed limit value, also in case of sensor failure
3
Alarm C, band transgression around the setpoint, also in case of sensor failure
4
Alarm B, fixed limit value, alarm at under-temperature, also in case of sensor
0 to ± scope of measuring range [phys. unit]
A1.A
A1.b
measuring range: dI.L to dI.H [phys. unit]
HY.1
0 to 10th part of the scope of the measuring range [phys. units]
0 to + scope of the measuring range [phys. units]at dP = 3
A1.C
0 to - scope the of measuring range [phys. unit]
0 to 10th part of the scope of the measuring range [phys. units]
0 to + scope of the measuring range [phys. units]at dP = 3
A1.C.
0 to + scope of the measuring range [phys. unit]
0 to 10th part of the scope of the measuring range [phys. units]
0 to + scope of the measuring range [phys. units]at dP = 3
dP
0
Display without decimal point
1
Display with 1 decimal
2
Display with 2 decimals
3
Display with 3 decimals
dI.L
Displayed value at start of scale, -999 to dI.H-1 [phys. unit]
dI.H
Displayed value at full scale, dI.L+1 to 9999 [phys. unit]
SP.L
usually dI.L to SP.H [phys. unit] SP.L = SP.H: fixed setpoint
SP.H
usually SP.L to dI.H [phys. unit]
SP.2
dI.L to dI.H [phys. unit], switch over via digital input SP.2
SP.r
0 to scope of measuring range [phys. unit (°C) per min/hour]
rA.d
0
phys. unit/min, rising and falling setpoint ramp
1
phys. unit/min, only rising setpoint ramp
2
phys. unit/min, only falling setpoint ramp
3
Ramp deactivated (similar to SP.r = 0)
4
phys. unit/hour, rising and falling setpoint ramp
5
phys. unit/hour, only rising setpoint ramp
6
phys. unit/hour, only falling setpoint ramp
Koepffstraße 5
D-74076 Heilbronn
6490B / 6490B-y / 6590B
failure
SP.L > SP.H: two setpoints
Telefon (07131) 1500-0
Page 31
e.g. 1234
e.g. 123.4
e.g. 12.34
e.g. 1.234
}
not valid
for SP.2