Command Location 2A: Event Reporting
Default Values
Digit Position (1): Shunt Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (2): Restore Receiver Select
See Digit Position (1) for programming options.
Digit Position (3): Unit Status Report Code
Valid entries are 0 - F.
The panel will add a fixed extension digit when reporting in 3/1 Extended, 4/2, and CFSK
formats. Fixed codes are listed below.
Program a 0 to disable Unit Status Reporting.
Digit Position (4): Unit Status Receiver Select
See Digit Position (1) for programming options.
Digit Position (5): Cancel Report Code
Valid entries are 0 - F.
The panel will add the User ID # as the second digit when reporting
in 3/1 Extended, 4/2, and CFSK formats.
Program a 0 to disable Cancel Reports.
Digit Position (6): Cancel Report Receiver Select
See Digit Position (1) for programming options.
UNIT STATUS FIXED EXTENSION CODES
1 = Low battery
2 = AC fail
3 = Bell fuse fail
4 = Loop trouble
5 = Failed to communicate
6 = Battery restore
Command Location 2B: Test Report
Default Values
Digit Positions (1) and (2): Test Report Code
Valid entries are 0 - F.
Only Position (1) is sent for 3/1 and 4/1 formats.
Positions (1) and (2) are sent for 3/1 Extended, 4/2, and CFSK formats.
Program 00 to disable Test Reports.
Digit Positions (3): Test Report Receiver Select
0 = Receiver 1 with Receiver 2 as back-up
1 = Receiver 1 only
Digit Positions (4): Test Report Interval
1 = 1 hour
4 = 12 hours
2 = 2 hours
5 = 24 hours
3 = 4 hours
6 = 7 days
2
See also CL 17 - 1E
Digit Positons (5 & 6)
See also CL 17 - 1E
Digit Positions (3 & 4)
7 = AC restore
8 = Bell fuse restore
9 = Loop trouble restore
A = not used
B = Watchdog reset
C = Completed programming
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
7 = 14 days
0 = 1 hour if armed
8 = 21 days
1 = 2 hours if armed
9 = 30 days
2 = 4 hours if armed
Command Location 2A and 2B
1
1
A
A
(1)
(2)
(3)
Hexadecimal Value
0
2
B
(1)
3 = 12 hours if armed
4 = 24 hours if armed
16
1
D
1
#
(4)
(5)
(6)
PROGRAMMING CONVERSIONS
Key Strokes
A
B
C
D
E
F
0
1
6
#
(2)
(3)
(4)
NOTE: CL A0 must be programmed
to correctly set time of test.
0
1
2
3
4
5

Advertisement