(8) F0- External DC fan error (3-core terminal motor)

Cause: Our frequency changing external unit uses the 3-lead-wire DC
motor, or "externally driven DC motor" for short, after 2012. It has no
speed feedback circuit but 3 drive lead wires and its driving principle is
Explanation of
similar to that of the compressor. The main control panel will indicate
"external DC fan error" when it detects imbalanced current on the three
error
lead wires of the driving motor.
Inspection path: Is the DC fan stuck by foreign matters→Motor
terminal connectors→Main external control panel→Motor
Tools required
Main external control panel in normal condition
for inspection
Frequent
Mechanical jam of external fan, main external control panel, external
DC motor
problematic part
1. First exclude the possibility of mechanical jam of external fan
blades.。
2. Observe if the terminal of the fan is not connected firmly or the
order of lead wires is correct. If the external fan of the newly installed
air conditioner rotates reversely, first observe if the color order of the
three lead wires is correct, or change the order of any two of the three
Inspection
lead wires of the motor to see if the fan can rotate in the forward
direction.
procedure and
3. The DC motor of this scheme is relatively simple and reliable, so the
key points
problem is more likely to be caused by the drive part of the fan of the
main external control panel. The maintenance personnel may as well
prepare matched main external control panel before maintenance. If the
fan returns to normal after replacing the main control panel, then it's
the main control panel problem; if it still indicates external DC motor
error, then replace the external DC motor.
Unlike the 5-core internal DC motor, there will be a process of fan
blade position locking before the 3-core DC motor with external drive
Special attention
starts to rotate. The fan blades will shake mechanically for 3-5 seconds
and then rotate slowly, which is normal phenomenon.

(9) F1 -Module protection error

Cause: The power module is the part to directly drive the compressor
to work. It can protect the machine in time when overcurrent,
overvoltage or overheat occurs and stops the compressor from
working. It will, at the same time, send "shutdown request" to the
Explanation of
module panel. The error triggered by the "shutdown request" is called
error
"module protection error".
Inspection path: Supply voltage → Compressor wire, reactor wire →
System blocked → Module panel damaged → Main external control
panel destroyed → Compressor destroyed
47