Object 6046: Vl_Velocity_Min_Max_Amount; Object 6048H: Vl_Velocity_Acceleration; Object 6049: Vl_Velocity_Deceleration; Object 604A: Vl_Velocity_Quick_Stop - Toshiba TOSVERT VF-MB1 Series Manual

Using canopen communication function
Hide thumbs Also See for TOSVERT VF-MB1 Series:
Table of Contents

Advertisement

5.1.7. Object 6046: vl_velocity_min_max_amount

This object indicates the configured minimum and maximum amount of velocity (unit min
vl_velocity_max amount sub-object is mapped internally to the vl_velocity_max positive and
vl_velocity_max negative values. The vl_velocity_min amount sub-object is mapped internally to the
vl_velocity_min positive and vl_velocity_min negative values.
At initial configuration, the Upper limit frequency (ul) and Lower limit frequency (ll) of the drive may
be not same value with Object 6046 setting value. And when change the Upper limit frequency and the
lower limit frequency of the drive parameter, Object 6046 value is different with the drive parameters. To
correspond these limit value, set Object 6046. And if need, execute Store Parameters command (Object
1010) to save the parameter to EEPROM.

5.1.8. Object 6048h: vl_velocity_acceleration

This object indicates the configured delta speed and delta time of the slope of the acceleration ramp.
-1
Unit is min
.
Velocity Acceleration Delta Speed
Velocity Acceleration Delta Time
Note: Do not change the acceleration/deceleration time unit (parameter f519), if change the
parameter, the setting value range will be different from above range.

5.1.9. Object 6049: vl_velocity_deceleration

This object shall indicate the configured delta speed and delta time of the slope of the deceleration ramp.
-1
Unit is min
.
Velocity Deceleration Delta Speed
Velocity Deceleration Delta Time
Note: Do not change the acceleration/deceleration time unit (parameter f519), if change the
parameter, the setting value range will be different from above range.

5.1.10. Object 604A: vl_velocity_quick_stop

This object indicates the configured delta speed and delta time of the slope of the deceleration ramp for
quick stop. Unit is min

5.1.11. Object 605A: Quick stop option code

This object shall indicate what action is performed when the quick stop function is executed.
The slow down ramp is the deceleration value of the used mode of operations.
Value
-32768 to -1
0
+1
+2
+3
+4
+5
+6
+7
+8
+9 to +32 767
: 225 ~ 30,000 min-1
: 0 ~ 3600 s
: 225 ~ 30,000 min-1
: 0 ~ 3600 s
-1
.
No function
Disable drive function
Slow down on slow down ramp and transit into Switch On Disabled
Slow down on quick stop ramp and transit into Switch On Disabled
Do not set
Slow down on voltage limit and transit into Switch On Disabled
Slow down on slow down ramp and stay in Quick Stop Active
Slow down on quick stop ramp and stay in Quick Stop Active
Do not set
Slow down on voltage limit and stay in Quick Stop Active
Reserved
- 28 -