Object 6040H: Controlword - Toshiba TOSVERT VF-MB1 Series Manual

Using canopen communication function
Hide thumbs Also See for TOSVERT VF-MB1 Series:
Table of Contents

Advertisement

5.1.2. Object 6040h: Controlword

15
ms
MSB
ms = manufacturer-specific;
r = reserved;
oms = operation mode specific;
h = halt;
fr = fault reset;
eo = enable operation;
qs = quick stop;
ev = enable voltage;
so = switch on
CW: Controlword (6040)
SW: Statusword (6041)
(CW: xxxx xxxx 0xxx x110 )
(CW: xxxx xxxx 0xxx x110)
(CW: xxxx xxxx 0xxx x111 )
(CW: xxxx xxxx 0xxx 1111 )
(CW: xxxx xxxx 0xxx xx0x)
Command coding (CiA DS402-2 DSP V3.0 Table 27)
Command
Shutdown
Switch on
Switch on + enable
operation
Disable voltage
Quick stop
Disable operation
Enable operation
Fault reset
NOTE Automatic transition to Enable operation state after executing SWITCHED ON state functionality.
When detects main power loss or not release main power loss in 3 sec after change to "Switch
11
10
9
8
r
oms
h
Bold bits shall be supported, other may be supported.
START
0
Not Ready to switch on
SW: xxxx xxxx x0xx 0000
1
Switch on disabled
SW: xxxx xxxx x1xx 0000
2
8
Ready to switch on
SW: xxxx xxxx x0 1x 0001
3
Switch on
SW: xxxx xxxx x01x 0011
4
Operation enable
SW: xxxx xxxx x01x 0111
9
Bits of the Controlword
fault
enable
reset
operation
Bit 7
Bit 3
0
x
0
0
0
1
0
x
0
x
0
0
0
1
x
- 25 -
7
6
5
fr
oms
From any state
Fault reaction active
SW: xxxx xxxx x0 xx 1111
SW: xxxx xxxx x0xx 1000
7
(CW: xxxx xxxx 0 xxx x01x)
( CW: xxxx xxxx 0xxx xx0x)
6
(CW: xxxx xxxx 0 xxx x110)
5
(CW: xxxx xxxx 0 xxx 0 111)
16
11
(CW: xxxx xxxx 0xxx x01x)
Quick
enable
stop
voltage
Bit 2
Bit 1
1
1
1
1
1
1
x
0
0
1
1
1
1
1
x
x
E6581692
4
3
2
1
eo
qs
ev
13
14
Fault
15
(CW: xxxx xxxx 1xxx xxxx)
10
(CW: xxxx xxxx 0 xxx x01x)
(CW: xxxx xxxx 0 xxx xx0 x)
Quick stop active
SW: xxxx xxxx x00x 0111
switch on
Transitions
Bit 0
0
2, 6, 8
1
3
3 + 4
1
Note
x
7, 9, 10, 12
x
7, 10, 11
1
5
1
4, 16
x
15
0
so
LSB
12