The set point is adjusted by turning the captive adjustment screw (see Fig. 8).
Allow pressure switch to reach the desired switch pressure.
Turn adjustment screw clockwise or counterclockwise to actuate the micro switch.
IMPORTANT
Please consult the wiring diagram for the contact status at atmospheric pressure (see Fig. 6).
Precise adjustment of set point to actuate on increasing pressure
Lower system pressure to 0 bar.
Increase pressure slowly and check if micro switch is actuated at desired switch pressure.
If necessary, readjust by turning the adjustment screw
Repeat preceding steps until microswitch operates at desired switch pressure.
Precise adjustment of set point to actuate on decreasing pressure
Increase pressure up to a point clearly above the desired switch pressure
pressure plus max. hysteresis; not above max. operating pressure).
Lower pressure slowly and check if micro switch is actuated at desired switch pressure.
If necessary, readjust by turning the adjustment screw
Repeat preceding steps until microswitch operates at desired switch pressure.
Following the adjustment of all set points, each set point must be checked and, if necessary, be
readjusted.
Electrical connections
, dimensions in mm (inch)
Cable ø 6...8 (0.23...0.31)
PL1*
CA1/2
Fig. 5:
* Standard: PL1, all others optional – only on request
Wiring code (contact status at atmospheric pressure)
PL 1
PL 2/3
1
1
C
2
2
NC
3
4
NO
---
3
PE
Fig. 6:
Wiring Code
6
(at least, switch
½" NPT
DIN 72585
M 12×1
PL2/3/5
CD0/1
Housing top edge
PL 4
PL 5
CA 1/2
old
new
no.
1
1
BN
1
2
2
BK
2
3
4
BU
GY
3
---
---
GN/YE
GN/YE
Use in Hazardous Locations
The pressure switches type Series 8000 with optional Ex i are approved for applications in
hazardous locations for intrinsically safe circuits. Units designed for intrinsically safe Ex i
application must be operated with a switch amplifier (see Fig. 7).
They are only for use in an approved intrinsically safe circuit.
Units with explosion-proof enclosures must be operated in accordance with their approval.
Approval class and identification characteristics according to type plate information must always be
observed. The models having light-alloy (aluminium) enclosures or enclosure parts must be
protected against all impact or friction which can ignite the explosive atmosphere. EC-design
approved types are marked with a label according to ATEX 94/9/EC.
The wiring between switch and Ex i isolation amplifier must meet the local safety requirements.
The customer must provide for a highly conductive connection between switch and grounding.
Unprotected area
Zener barrier type
Switch amplifier NAMUR
Fig. 7: Operation of pressure switches in intrinsically safe areas
7

Maintenance/Cleaning

Maintenance
PL4
The pressure switch is maintenance free. Checking the set points lies within the discretion of the
user. The usual preventive maintenance work in accordance with the PED and ATEX guidelines
must always be carried out.
Please note that small setpoint drifts may occur during the initial use of the switch (run-in period).
To minimize the setpoint drift we can perform a run-in (ageing) process in our works on request.
Larger or continuing setpoint drifts during the normal use of the switch may indicate that the
measuring system is not used correctly within the specified limits, exceeding the design criteria or
CD 0
CD 1
is worn-out. This might lead to metal fatigue of the measuring system and it therefore should be
replaced before an ultimate rupture of the metal diaphragm might take place. Please consult your
supplier or Barksdale directly for guidelines.
VT
VT
BU
BU
RD
RD
---
GN
Ex ia area
c
NO
NC
GRD
7