Configuration With Siemens S7 Controller; Fig. 28 Configuration Of The Profibus Dp I/O Modules - Appending The Bus Terminals; Fig. 29 Busklemn.bmp; Fig. 30 Busklems.bmp - Beckhoff BK3 0 Series Documentation

Bus coupler for profibus-dp
Table of Contents

Advertisement

Parameterization and commissioning
Fig. 28: Configuration of the PROFIBUS DP I/O modules - appending the Bus Terminals
4.4.8

Configuration with Siemens S7 controller

4.4.8.1
Configuration: Siemens S7 Controller
Inserting the images
In order to assign an image to the devices in the Siemens software, they must be copied into the
Step7 \ S7Data \ NcBmp directory.
Fig. 29: Busklemn.bmp
Fig. 30: Busklems.bmp
Inserting the GSD files
• Go to Extras \ Install new GSD in the hardware catalog for your Step7.
• Select the directory in which the Beckhoff GSD is located, and import the files.
• It can then be found in the hardware catalogue under PROFIBUS DP \ Further field devices \ I/O.
4.4.8.2
Configuration: Siemens S7 Controller BK3120
Parameter data for the BK3120
Settings
46
Version: 4.3.0
BK3xx0