4.4.3

Configuration of Complex Modules

After the DP modules for the activated functions of the Bus Coupler have been added to the Bus Coupler in
the DP configuration tool, the next step is for the complex terminals (KL15xx, KL25xx, KL3xxx, KL4xxx,
KL5xxx, KL6xxx, KL8xxx) to be added in the sequence in which they are plugged in, regardless of whether
digital terminals are plugged in between the complex terminals, or of how many there may be:
Complex function
Description
module
KL1501
KL1501
KL2502
KL2502
KL2521
KL2521
KL3351 compact
KL3351 - only the 16 bit input value is transmitted
KL3351 complex
KL3351 - 24 bits of input/output are transmitted, so that
access can be had to the terminal's registers in addition to
transmission of the 16 bit input value
KL3361
KL3361
KL3xx2 compact
All KL3xx2 - only the 16 bit input value of each channel is
transmitted
KL3xx2 complex
Old KL3xx2 - 24 bits of input/output are transmitted for each
channel, so that access can be had to the terminal's
registers in addition to transmission of the 16 bit input value
KL3xx4 compact
All KL3xx4 - only the 16 bit input value of each channel is
transmitted
KL3xx4 complex
Old KL3xx4 - 24 bits of input/output are transmitted for each
channel, so that access can be had to the terminal's
registers in addition to transmission of the 16 bit input value
KL4xx2 compact
All KL4xx2 - only the 16 bit output value of each channel is
transmitted
KL4xx2 complex
Old KL4xx2 - 24 bits of input/output are transmitted for each
channel, so that access can be had to the terminal's
registers in addition to transmission of the 16 bit input value
KL4xx4 compact
All KL4xx4 - only the 16 bit output value of each channel is
transmitted
KL4xx4 complex
Old KL4xx4 - 24 bits of input/output are transmitted for each
channel, so that access can be had to the terminal's
registers in addition to transmission of the 16 bit input value
BK3xx0
Version: 4.3.0
Parameterization and commissioning
Associated CfgData (as
hex code)
0xB4 (in GSD file)
0xB5 (alternatively)
0xF2 (alternatively)
0xB5 (in GSD file)
0xB2, 0xB2 (alternatively)
0xF2 (alternatively)
0xB2 (in GSD file)
0xF1 (alternatively)
0x51 (in GSD file)
0x50, 0x50 (alternatively)
0xB5 (in GSD file)
0xB2, 0xB2 (alternatively)
0xF2 (alternatively)
0xFB (in GSD file)
0x51 (in GSD file)
0x50, 0x50 (alternatively)
0xB5 (in GSD file)
0xB2, 0xB2 (alternatively)
0xF2 (alternatively)
0x53 (in GSD file)
0x51, 0x51(alternatively)
0x50, 0x50, 0x50, 0x50
(alternatively)
0xBB (in GSD file)
0xB5, 0xB5 (alternatively)
0xB2, 0xB2, 0xB2, 0xB2
(alternatively)
0xF5 (alternatively)
0x61 (in GSD file)
0x60, 0x60 (alternatively)
0xB5 (in GSD file)
0xB2, 0xB2 (alternatively)
0xF2 (alternatively)
0x63 (in GSD file)
0x61, 0x61 (alternatively)
0x60, 0x60, 0x60, 0x60
(alternatively)
0xBB (in GSD file)
0xB5, 0xB5 (alternatively)
0xB2, 0xB2, 0xB2, 0xB2
(alternatively)
0xF5 (alternatively)