Parameterization and commissioning
Digital outputs
11 x KL2xx4, i.e. 10 x 4 bit = 44 bit
44 bit  / 8 = 5.5 bytes, rounded up to 6 bytes, i.e. enter  6 x 8 bit or 1 x 48 bit or 1 x 8 bit + 1 x 40 bit etc. (see
Fig. Example for entering individual bytes and Fig. Example for entering contiguous bytes)
Fig. 32: Example for entering individual bytes.
Maximum config data
Each individual byte requires one byte of ConfigData. In the BK3120 a maximum of 64 bytes of con-
figuration data is available.
48
Version: 4.3.0
BK3xx0