Fig. 31: Parameter data for the BK3120
Parameter data
DPV1 service (class 1)
Reaction to Bus Terminal error
Terminal bus diagnostics
Digital terminal diagnostic data
Data format
K-Bus mode
Fast FreeRun mode
Reaction to DP errors
Reaction to K-bus errors
Configuration of the BK3120 module with digital inputs/outputs only
Sample 1:
1 x BK3120
10 x KL1xx4
1 x KL9100 (is not entered, as this Bus Terminal is entirely passive)
11 x KL2xx4
1 x KL9010 (is not entered, as this Bus Terminal is entirely passive)
The sum total of digital bytes must be added together and entered.
Digital inputs
10 x KL1xx4, i.e. 10 x 4 bits = 40 bits
40 bit / 8 = 5 bytes, i.e. enter 5 x 8 bit or 1 x 40 bit or 1 x 8 bit + 1 x 32 bit, etc. (see Fig. Example for
entering individual bytes and Fig. Example for entering contiguous bytes)
BK3xx0
Name
DPV1 Services [} 56]
Reaction to Bus Terminal error [} 69]
PROFIBUS diagnosis [} 70]
Digital Bus Terminal diagnostics [} 70]
Data format [} 35]
K-bus update [} 53]
Fast FreeRun mode [} 53]
Reaction to fieldbus error [} 35]
Reaction to K-bus errors [} 35]
Version: 4.3.0
Parameterization and commissioning
47