Dp Diagnostics; Dp Diagnostic Data (Diagdata) - Beckhoff BK3 0 Series Documentation

Bus coupler for profibus-dp
Table of Contents

Advertisement

Diagnostics and error handling
Error code
Error code argu-
ment
9 pulses
0
13 pulses
0
14 pulses
n
15 pulses
n
16 pulses
n
17 pulses
n
18 pulses
n
Error location
The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals,
such as a power feed terminal, are not included in the count.
6.2

DP diagnostics

6.2.1

DP Diagnostic Data (DiagData)

The DP diagnostic data consists of six bytes of DP standard diagnosis, along with up to 238 bytes of device-
specific diagnostic data. The device-specific diagnostic data for Beckhoff slaves is represented in the DPV1
status message.
When the DP diagnostic data changes, the slave reports this fact to the master, and the master will
automatically fetch the changed diagnostic data. This means that DP diagnostic data is not included in the
DP process data in real-time, but is always sent to the controller a few cycles later.
In TwinCAT the DP diagnostic data is read from the DP Master interface (FC310x, CX1500-M310) using
ADS (see the section describing Slave Diagnosis in the FC310x documentation).
64
Description
Checksum error in program
flash memory
Runtime K-bus command error One of the Bus Terminals is
Bus Terminal n has the wrong
format
Number of Bus Terminals is no
longer correct
Length of the K-bus data (bit
length) is no longer correct. n =
bit length after booting
Number of Bus Terminals is no
longer correct.
n = number of Bus Terminals
after booting
Bus Terminal identifier no
longer correct after reset (n =
Bus Terminal number).
Version: 4.3.0
Remedy
Set manufacturer's setting with the
KS2000
defective; halve the number of Bus
Terminals attached and check
whether the error is still present
with the remaining Bus Terminals.
Repeat until the defective Bus
Terminal is located.
Start the coupler again, and if the
error occurs again then exchange
the Bus Terminal
Start the coupler again, and if the
error occurs again after this, use
the KS2000 software to set
manufacturer's settings
BK3xx0