Emerson Fisher FLOBOSS 407 Instruction Manual page 102

Field automation systems, flow manager
Table of Contents

Advertisement

FloBoss 407 Instruction Manual
FIELD WIRING
A: Positive (field device power)
TERMINALS
B: Negative
C: Not Used
OUTPUT
Type: Solid-state relay, normally-
open.
Active Voltage: 11 to 30 Vdc.
Active Current: Fuse-limited to 1.0
amps continuous at 75 °C
(167 °F), externally supplied.
Inactive Current: Less than 100
µA at 30 Vdc.
Frequency: 0 to 10 Hz maximum.
VIBRATION
20 Gs peak or 0.06 in. double
amplitude, 10 to 2,000 Hz, per MIL-
STD-202 method 204 condition F.
MECHANICAL
1500 Gs 0.5 mS half sine per MIL-
SHOCK
STD-202, method 213, condition F.
WEIGHT
1.3 ounces (37 grams) typical.
Solvent-resistant thermoplastic
CASE
polyester, meets UL94V-0. Dimen-
sions are 0.6 in. D by 1.265 in. H by
3-46
Isolated Module Specifications
POWER
REQUIRE-
MENTS
OUTPUT
ISOLATION
Common Specifications
CASE
(CONT'D)
ENVIRON-
MENTAL
APPROVALS
4.9 to 5.1 Vdc. 1 mA in "Off"
state; 6 mA in "On" state.
Isolation: 100 megohm
minimum, input to output, and
input or output to case.
Voltage: 4,000 Vac (RMS) mini-
mum, input to output.
Capacitance: 6 pF typical, input
to output.
1.690 in. W (15 mm by 32 mm by
43 mm), not including pins.
Meets the Environmental specifi-
cations of the ROC or FloBoss in
which the module is installed,
including Temperature and Tran-
sient Protection specifications.
Approved by CSA for hazardous
locations Class I, Division 2,
Groups A, B, C, and D.
Rev 5/00