(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Intake temperature (TH1)
Indoor pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Pressure saturation temperature (T
Outdoor pipe temperature (TH3)
Outdoor discharge pipe temperature (TH4)
Outdoor 2-phase pipe temperature (TH6)
Outdoor air temperature (TH7)
Temperature difference code (intake temperature - set temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
*1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors
to open/short. And the unit runs emegency operation with the values listed above.
*2: If one thermistor is set to open/short, the values for each will be different from the list above.
*3: Only for VHA2, YHA2
[Example] When pipe temperature thermistor (TH3) has an open or short circuit.
Thermistor
TH3
TH6
Regard normal figure as effective data.
TH4
Regard normal figure as effective data.
TH5
TH2
T
(*3)
63HS
Regard normal figure as effective data.
OCH425F
)
63HS
COOL
HEAT
5
45
Tb
Ta
Td
Tc
5
50
45
5
Tf
Te
Operation mode
COOL
HEAT
27
20.5
5
45
5
50
25
22
50
50
(*1, *3)
45
5
(*1)
(*1)
80
80
50
(*1)
5
35
7
(*1)
5
5
30deg
(*2)
30deg
5deg
5deg
(*2)
<VHA, YHA>
Discharge superheat (SHd)
Cooling = TH4 - TH6 = Tc - Ta
Heating = TH4 - TH5 = Td - 50
Degree of subcooling (SC)
Cooling = TH6- TH3 = Ta -45
Heating = TH5- TH2 = 50 - 45 = 5 deg.
<VHA2, YHA2>
Discharge superheat (SHd)
Cooling = TH4 - T
= Tc - Te
63HS
Heating = TH4 - T
= Td - Tf
63HS
Degree of subcooling (SC)
Cooling = T
- TH3 = Te - 45
63HS
Heating = T
- TH2 = Tf - 45
63HS
68
Remarks
—
—
—
—
—